2.3 Application Address
An Application Address is used together with a Group or Area Address to identify one or more units,
inputs or outputs. It provides a convenient way to separate units and their associations, into different
categories. The default Application Address is “lighting”. The programmer can specify up to 255
Application Addresses.
Using two address types provides thousands of unique Group Address combinations, instead of
the 255 which would be available if only a single Application Address was used. This means that a
message to switch an output within the lighting application, will not affect an output within the heating
application, even if both outputs used the same Group Address.
It is recommended that specific Application Addresses are used for particular applications. (Special
features may be associated with these Application Addresses in the future). These are listed in Table
2. Other Application Addresses may be used for different applications.
Application Application Address
Free use for developers 000 to 015 (00h to 0Fh)
Temperature Broadcast 025 (19h)
Room Control System (Clipsal 5 Star) 038 (26h)
Lighting 048 to 094 (30h to 5Eh)default is 056 (38h)
Dali Gateway Interface Default Application 095 (5Fh)
Ventilation (dampers and fans) 112 (70h)
Irrigation control 113 (71h)
Pool, spa, fountain and pond control 114 (72h)
Heating 136 (88h)
Trigger control 202 (CAh)
Enable control 203 (CBh)
Audio / Visual 205 (CDh)
Security 208 (D0h)
Metering (gas, water, electricity, oil, etc) 209 (D1h)
Clock and Timekeeping 223 (DFh)
Telephony Status and Control 224 (E0h)
Measurement (light, liquid, temperature, etc) 228 (E4h)
C-Bus Network Management and Control 255 (FFh)
Table 2 –Application Address assignments