C-Bus™ Basic Programming 1250SM0904R10/09
C-Bus™ Products Training Course 10/2009
98 © 2009 Schneider Electric. All Rights Reserved.
Figure 78 - The Recovery tab of a relay
Restrike Delay Tab
Many lighting devices such as high bay lamps (typically, metal halide or
Sodium Vapour lamps) require a minimal period to cool down before being
turned on again (restriking).
The Restrike Delay tab provides the means for setting a global restrike
delay interval on a channel by channel basis. If you have lamps that require
a cooling down period, then you can add a restrike delay by selecting the
relevant channels (using the check boxes), and setting the delay interval
using the restrike delay.
Figure 79 - The Restrike Delay tab of a relay
The image below shows the behaviour of a relay channel with a 10 minute
restrike delay programmed into it. You will see that all ON and OFF
commands that are sent during the delay period are ignored for that
particular channel. Once the 10 minute restrike delay is over, the relay will
change to the current state of the group address that its controlled by.