C-Bus™ Basic Programming 1250SM0904R10/09
C-Bus™ Products Training Course 10/2009
120 © 2009 Schneider Electric. All Rights Reserved.
Figure 105 - The Key Functions tab
Here you will see that each key/button consists of 4 micro functions, which
are programmed into 4 parameters called:
Short Press
Short Release
Long Press
Long Release.
The figure below helps to explain when the micro functions are issued.
Time
OFF
Mechanical Switch Level
ON
48ms
Debounce
Ignored
400ms
Long Press
If the Key is released between
the Debounce & Long Press
times, the SHORT RELEASE
Micro Function is issued.
If the Key is released after
the Long Press times, the
LONG RELEASE Micro
Function is issued.
The SHORT PRESS Micro
Function is issued once the
debounce time has been
reached.
The LONG PRESS Micro
Function is issued once
the Long Press time has
been reached.
Figure 106 - When the micro functions are sent