C-Bus™ Basic Programming 1250SM0904R10/09
C-Bus™ Products Training Course 10/2009
102 © 2009 Schneider Electric. All Rights Reserved.
Figure 84 – The Unit Identification tab of a DIN rail dimmer
The Unit Identification tab will display the:
name of the Toolkit project
C-Bus network that the unit is on
unit address of the C-Bus device
firmware version of the C-Bus device
serial number of the unit
catalogue number of the unit.
The table below highlights the more important parameters in the Unit
Identification tab.
Parameter Description
Part Name Assigns a name to the C-Bus unit, to help identify its physical location.
This is an 8 character name which is physically stored in the dimmer.
Application Selects the application address that the dimmer will operate on.
Area Specifies an area address for all dimmer channels to respond to.
Tag Name Assigns a more meaningful name to the C-Bus dimmer. This is only stored
in the C-Bus database.
Notes Documents any nonstandard information about the programming,
installation or application the C-Bus dimmer. This is only stored in the
C-Bus database.
Table 32 - Important parameters on the Unit Identification tab
NOTE: The Unit Identification tab is common and identical for almost all
C-Bus units.
Logic Tab
The Logic tab is separated into two parts:
logic assignments
logic recovery
The Logic Assignments allows you to configure 4 low level MIN / MAX
operations on the dimmer. This means that the control of the selected
channels will be dependant on the Level (0% to 100%) of the associated
logic group.
The Logic Recovery will determine the behaviour of the logic group. Logic
Recovery will affect the level (0% to 100%) that the logic group will return to
after power up, allowing the selection of:
N/C (no change, which restores to its previous level)
OFF
a level (1% to 99% which is technically ON when using a relay)
ON