1250SM0904R10/09 C-Bus™ Basic Programming
10/2009 C-Bus™ Products Training Course
© 2009 Schneider Electric. All Rights Reserved. 43
Any programmed associations between input and output units can be
overwritten by a Learn Mode association. To ensure that existing
programming is not overwritten, only use each output channel and each
button on an input once.
Learn Mode Operations
C-Bus Learn Mode can be used to create a variety of flexible control
configurations. Basic On/Off switches can be configured as well as Dimmer
and Timer controls.
Relay and Dimmer Configurations
The type of control function assigned to the button on an input unit, depends
on whether Learn Mode is exited via a relay or dimmer output unit:
For a switching control function, exit on a relay unit.
For a dimmer function exit Learn Mode on a dimmer unit.
When a C-Bus relay output unit is used to exit Learn Mode, any buttons (on
input units) included in that Learn Mode association will be programmed
with the On/Off key function.
When a C-Bus dimmer output unit used to exit Learn Mode, any buttons (on
input units) included in that Learn Mode association will be programmed
with the Dimmer key function.
Two Button Configurations
The single button On/Off or Dimmer configuration may be extended so that
one button turns the load on, and one turns it off. This is done during Learn
Mode by pressing two adjacent buttons on the same input unit.
After exiting from Learn Mode, the:
first button will turn the load on
second button will turn the load off.
When the On button on the input unit is pressed the indicators on both
buttons will light up, since they are both associated with the same load.
When the Off button on the input unit is pressed, the indicators will both turn
off.
This configuration may also be applied when using C-Bus dimmers. Where
one button on and input is assigned a Dimmer Up key function, and the
other button is assigned a Dimmer Down key function.
Area Address Switching
Area address switching functions give the ability to provide a Master On/Off
switch that turns all lights and loads on or off simultaneously.
It is assumed that the primary function of the button is intended to be as a
Master Off switch. Hence a short press of the button will instantaneously
turn off all selected lights and loads. A long press on the button will turn
them all on.
To implement area address switching:
1) Set the network into Learn Mode.