1250SM0904R10/09 C-Bus™ Basic Programming
10/2009 C-Bus™ Products Training Course
© 2009 Schneider Electric. All Rights Reserved. 121
Micro Function Action
Idle No action
Store 1 This stores the current level in the Recall 1 memory location (Blocks tab).
When the Recall 1 function is used, the group address reverts to this
level. The level is stored in non-volatile memory. No transmission is
made over the C-Bus Network.
Downcycle The output level is ramped down to minimum. If the output is already at
minimum, it ramps up to maximum. The Downcycle function should be
used in conjunction with the End Ramp function to ensure that ramping
ends at the desired level. The direction of output ramping changes with
each successive Downcycle/End Ramp operation. This allows a single
button to act as an up / down light dimmer. The Off Key function can be
used to terminate ramping if required. A RAMP TO LEVEL message is
transmitted over the C-Bus network.
Memory Toggle If the output is on, the Memory Toggle function stores the current level in
the Recall 2 memory location (Blocks tab) and switches the output off. If
the output is off, the function sets the output to the last level stored in the
Recall 2 memory location (the previous brightness level). An OFF or
RAMP TO LEVEL message is transmitted over the C-Bus network.
Down Key This function is similar to Downcycle except that it can only ramp the
output level downwards. The output will be ramped to the minimum level
unless either the End Ramp or Off Key function terminates the process
early. The ramp rate for the Down Key function is set by the Ramp 1
parameter (Global tab). The Down Key function has no effect if the
current output is in the off state. A RAMP TO LEVEL message is
transmitted over the C-Bus network.
Up Key The output level increases to the maximum level, unless either the End
Ramp or Off Key function ends the process early. The ramp rate for the
Up Key function is set by the Ramp 1 parameter (Global tab). If the
current level is already at a maximum, no action will occur. A RAMP TO
LEVEL message is transmitted over the C-Bus network.
Recall 1 The output level is set to the level stored in the Recall 1 memory location
(Blocks tab). A RAMP TO LEVEL message is transmitted over the C-Bus
network.
Recall 2 The output level is set to the level stored in the Recall 2 memory location
(Blocks tab). A RAMP TO LEVEL message is transmitted over the C-Bus
network.
Retrigger Timer The retrigger timer command starts the internal timer only if the output is
currently on (at any level). If the output is already on, the timer is
restarted. A RAMP TO LEVEL message is transmitted over the C-Bus
network.
Start The internal timer is started without affecting the output level (if the timer
value is greater than zero). An ON message may be transmitted over the
C-Bus network.
Ramp Off The output level is ramped to the minimum level and then switched off.
The ramp rate is set by the Ramp 2 parameter (Global tab). This function
cannot be interrupted by the End Ramp function. A RAMP TO LEVEL
message is transmitted over the C-Bus network.
Ramp Recall 1 The output level is ramped up or down (depending on the current level),
to the level stored in the Recall 1 memory location (Blocks tab). The
ramp rate is set by the Ramp 2 parameter (Global tab). This function
cannot be interrupted by the End Ramp function. A RAMP TO LEVEL
message is transmitted over the C-Bus network.